What the calculator does
It converts the battery bank into usable energy (watt-hours), applies the inverter's efficiency, and divides by the load to estimate runtime. It also reports the discharge current and the C-rate, which tells you whether the battery's printed capacity is realistic at that current, and the capacity you would need for a target runtime.
Formula
Runtime (h) = Usable energy × ηinverter ÷ Load (W)
Discharge current (A) = Load ÷ (ηinverter × Vbank)
C-rate = Discharge current ÷ Ahtotal
Capacity for target (Ah) = Load × hours ÷ (Vbank × DoD × ηinverter)
Ahtotal is the capacity per battery multiplied by the number of batteries or strings in parallel. Batteries in series raise the bank voltage but not the Ah.
Worked example
A 300 W load on a 12 V inverter with one 150 Ah flooded battery, 50 % depth of discharge and 85 % inverter efficiency.
- Usable energy = 12 × 150 × 0.5 = 900 Wh.
- Runtime = 900 × 0.85 ÷ 300 = 2.55 h, about 2 h 33 min.
- Discharge current = 300 ÷ (0.85 × 12) = 29.4 A, a C-rate of 0.196 (roughly C/5).
- For 4 hours: 300 × 4 ÷ (12 × 0.5 × 0.85) = 235 Ah, so two 150 Ah batteries in parallel (300 Ah) would be needed.
Why the printed Ah is not the whole story
Lead-acid capacity is rated at a slow 20-hour discharge (C20). Draw the same battery down in 5 hours and it delivers noticeably less than its rating; in 1 hour, much less. This is the Peukert effect. The calculator flags C-rates above C/5 (0.2 C) for lead-acid, where the shortfall becomes significant, and above 0.5 C for LiFePO4, which is far less affected. Use the flag as a prompt to add capacity or check the manufacturer's discharge curves; the calculator does not apply a Peukert correction itself.
Assumptions and limitations
- Constant load. Real loads vary; refrigerators and pumps cycle, and motors draw several times their running current at start.
- Healthy, fully charged batteries at moderate temperature. Capacity falls with age, sulphation and cold.
- Efficiency is treated as constant. Inverters are least efficient at light load; a 2 kW inverter running a 100 W load may be well under 80 % efficient. The inverter's own idle draw is not included: add it to the load if the datasheet gives it.
- No Peukert correction. High-rate discharges deliver less than the rating; see above.
- Not a charging or solar sizing tool. Recharge time, charger current and solar array sizing are separate calculations.
Frequently asked questions
Why not use 100 % depth of discharge?
Because it destroys lead-acid batteries quickly. Cycle life falls steeply with deeper discharge; 50 % is a common compromise between runtime and battery life. LiFePO4 tolerates 80–90 % routinely.
Does a 24 V or 48 V bank last longer than 12 V?
Not by itself: energy is volts × amp-hours, so the same batteries rearranged in series hold the same energy. Higher voltage does reduce current and cable losses, and inverters are often more efficient at 24 V or 48 V.
How do I find my load in watts?
Read it from each appliance label, or measure with a plug-in power meter. For appliances rated in amps, multiply by the mains voltage (e.g. 0.5 A × 230 V = 115 W). Add a margin for start-up surges on motors and compressors.
References
- IEC 61427-1:2013, Secondary cells and batteries for renewable energy storage — general requirements and methods of test; context for capacity ratings and cycling
- Peukert, W. (1897), "Über die Abhängigkeit der Kapazität von der Entladestromstärke bei Bleiakkumulatoren" — original description of capacity falling with discharge current