Electrical

Cable sizing calculator

Choose a copper conductor size to IEC 60364-5-52 from the design current and breaker rating, the installation method, PVC or XLPE insulation, ambient temperature and grouping, with the Ib ≤ In ≤ Iz coordination and the voltage drop over the route checked together.

Load, protection and route
The load's full-load current; use the power and current calculator to get it from kW or hp.
230 V line-to-neutral for single-phase; 400 V line-to-line for three-phase.
Along the cable from the distribution board to the load, not the round trip.
Conduit includes trunking and ducting on or in a masonry wall. Cables on trays, ladders or in free air (methods E, F, G) are not covered.
Air around the cable for A1, B1 and C (tables are for 30 °C); ground temperature at cable depth for D1 (tables are for 20 °C). Values between the 5 °C table rows are interpolated.
Circuits bunched in the same conduit, trunking or duct, or touching on a surface, including this one (Table B.52.17, item 1). Counts between the table's values take the next tabulated count.
MCB or MCCB rating; 0 for none. Standard ratings: 6, 10, 16, 20, 25, 32, 40, 50, 63, 80, 100, 125, 160, 200, 250 A.
Used for the voltage drop only; 1.0 for heaters and lighting, 0.8–0.9 for motors. Ignored for DC.
IEC 60364-5-52 Annex G recommends 3 % for lighting and 5 % for other uses from a public low-voltage supply.

Cable size

Enter your values and press Calculate.

What the calculator does

A cable has to pass three tests: it must carry its load current continuously without its insulation overheating in the place it is installed, it must be protected by a device that trips before the cable is damaged, and it must deliver an acceptable voltage at the far end. The calculator does the first two together, the way IEC 60364 frames them, and the third as a separate check. It takes the design current and the rating of the circuit breaker, derates the tabulated current-carrying capacities of IEC 60364-5-52 for the installation method, the insulation, the ambient temperature and the number of grouped circuits, walks up the standard copper sizes until the derated capacity covers the breaker rating, then works out the voltage drop over the route at the conductor's rated temperature and steps up again if the limit is exceeded. It reports which of the two checks decided the size, so you can see whether a cooler route, a smaller group or a shorter run would have allowed a smaller cable.

Enter 0 for the protective device if you only want the cable checked against the load current; the result is then a cable that still needs a breaker chosen to fit it. The power and current calculator converts a load in kW or hp to its full-load current, and the voltage drop calculator explores the drop alone for any size and temperature.

Formula

Coordination (IEC 60364-4-43, 433.1): Ib ≤ In ≤ Iz and I2 ≤ 1.45 × Iz

Derated capacity: Iz = It × Ca × Cg so the table value needed is It ≥ In ÷ (Ca × Cg)

Voltage drop: ΔV = k × Ib × L × r(θ) × cos φ, k = 2 for single-phase and DC, √3 for three-phase
r(θ) = R20 × (1 + 0.00393 × (θ − 20)), θ = 70 °C for PVC, 90 °C for XLPE

where Ib is the design current of the circuit, In the rated current of the protective device, It the current-carrying capacity tabulated in Annex B of IEC 60364-5-52 for the reference method and number of loaded conductors, Ca the temperature correction factor (Table B.52.14 for cables in air, B.52.15 for ducts in the ground), Cg the grouping reduction factor (Table B.52.17), L the one-way route length in metres and R20 the IEC 60228 class 2 conductor resistance at 20 °C, the same values the voltage drop calculator uses. The size is the first standard conductor whose Iz reaches In (or Ib when no device is entered), or the first whose drop is within the limit, whichever is larger.

I2 is the current that makes the protective device operate within its conventional time. For a miniature circuit breaker to IEC 60898-1 it is 1.45 × In, and for a moulded-case breaker to IEC 60947-2 it is 1.3 × In, so with either device In ≤ Iz satisfies the 1.45 condition on its own and the calculator does not test it separately. A gG fuse to IEC 60269 has I2 = 1.6 × In and therefore needs In ≤ 0.9 × Iz; if the circuit is fused, enter a rating 10 % above the fuse's.

Worked example

A 40 A single-phase load at 230 V, 40 m from the distribution board, wired with PVC-insulated single-core conductors in conduit on a wall (method B1) through a ceiling void that reaches 40 °C in summer, one circuit in the conduit, a 40 A MCB, power factor 0.85, voltage drop limit 5 %.

  1. Correction factors: Ca = 0.87 (PVC in air at 40 °C), Cg = 1.00 (a single circuit). The table value needed is It ≥ 40 ÷ (0.87 × 1.00) = 46.0 A.
  2. Table B.52.2, column B1: 6 mm² is rated 41 A, too small; 10 mm² is rated 57 A. Derated, Iz = 57 × 0.87 = 49.6 A, and 40 A ≤ 40 A ≤ 49.6 A, so the coordination holds.
  3. Voltage drop with 10 mm² at 70 °C: r = 1.83 ÷ 1000 × (1 + 0.00393 × 50) = 0.00219 Ω/m; ΔV = 2 × 40 × 40 × 0.00219 × 0.85 = 5.96 V, which is 2.59 % of 230 V and within the 5 % limit.
  4. Voltage drop on its own would have accepted 6 mm² (4.36 %), so the answer is 10 mm² copper, governed by current-carrying capacity.

Put the same circuit in a conduit that already carries two other circuits and Cg falls to 0.70: the table value needed becomes 40 ÷ (0.87 × 0.70) = 65.7 A, 10 mm² (57 A) no longer passes and 16 mm² (76 A) is the answer. At 45 °C as well, the factors multiply to 0.553, the required table value rises to 72.3 A and 16 mm² clears it with 42.0 A of derated capacity against the 40 A breaker.

Current-carrying capacity used: PVC 70 °C, copper (IEC 60364-5-52 Tables B.52.2 and B.52.4)

Size (mm²)A1B1CD1
1.514.5 / 13.517.5 / 15.519.5 / 17.522 / 18
2.519.5 / 1824 / 2127 / 2429 / 24
426 / 2432 / 2836 / 3237 / 30
634 / 3141 / 3646 / 4146 / 38
1046 / 4257 / 5063 / 5760 / 50
1661 / 5676 / 6885 / 7678 / 64
2580 / 73101 / 89112 / 9699 / 82
3599 / 89125 / 110138 / 119119 / 98
50119 / 108151 / 134168 / 144140 / 116
70151 / 136192 / 171213 / 184173 / 143
95182 / 164232 / 207258 / 223204 / 169
120210 / 188269 / 239299 / 259231 / 192
150240 / 216300 / 262344 / 299261 / 217
185273 / 245341 / 296392 / 341292 / 243
240321 / 286400 / 346461 / 403336 / 280
300367 / 328458 / 394530 / 464379 / 316

Amperes for one circuit at 30 °C in air (A1, B1, C) or 20 °C in the ground (D1). Each cell gives two loaded conductors (single-phase, DC) / three loaded conductors (three-phase). A1: insulated conductors in conduit in a thermally insulated wall. B1: insulated conductors in conduit, trunking or ducting on a wall. C: single-core or multicore cable clipped direct to a wall. D1: multicore cable in conduit or duct in the ground.

Current-carrying capacity used: XLPE 90 °C, copper (IEC 60364-5-52 Tables B.52.3 and B.52.5)

Size (mm²)A1B1CD1
1.519 / 1723 / 2024 / 2225 / 21
2.526 / 2331 / 2833 / 3033 / 28
435 / 3142 / 3745 / 4043 / 36
645 / 4054 / 4858 / 5253 / 44
1061 / 5475 / 6680 / 7171 / 58
1681 / 73100 / 88107 / 9691 / 75
25106 / 95133 / 117138 / 119116 / 96
35131 / 117164 / 144171 / 147139 / 115
50158 / 141198 / 175209 / 179164 / 135
70200 / 179253 / 222269 / 229203 / 167
95241 / 216306 / 269328 / 278239 / 197
120278 / 249354 / 312382 / 322271 / 223
150318 / 285393 / 342441 / 371306 / 251
185362 / 324449 / 384506 / 424343 / 281
240424 / 380528 / 450599 / 500395 / 324
300486 / 435603 / 514693 / 576446 / 365

Same conditions and layout as the PVC table. XLPE and EPR share these values. The 90 °C rating may only be used where the terminals and equipment the cable connects to are rated for it; many are limited to 70 °C.

Correction factors used (IEC 60364-5-52 Tables B.52.14, B.52.15 and B.52.17)

Temperature (°C)Air, PVCAir, XLPEGround (D1), PVCGround (D1), XLPE
101.221.151.101.07
151.171.121.051.04
201.121.081.001.00
251.061.040.950.96
301.001.000.890.93
350.940.960.840.89
400.870.910.770.85
450.790.870.710.80
500.710.820.630.76
550.610.760.550.71
600.500.710.450.65

Ambient factor Ca, reference 30 °C in air and 20 °C in the ground; the calculator interpolates linearly between rows. Grouping factor Cg for circuits bunched in air, on a surface, embedded or enclosed (Table B.52.17, item 1): 1 circuit 1.00, 2: 0.80, 3: 0.70, 4: 0.65, 5: 0.60, 6: 0.57, 7: 0.54, 8: 0.52, 9: 0.50, 12: 0.45, 16: 0.41, 20: 0.38; a count between tabulated values takes the next tabulated count.

Assumptions and limitations

  • Copper conductors, 1.5 to 300 mm², reference methods A1, B1, C and D1 only. Aluminium, multicore cables in conduit (A2, B2), cables on trays, ladders or in free air (E, F, G) and cables buried direct (D2) have their own columns in the standard and are not offered. For a multicore cable in conduit the B2 values are roughly 5–15 % below B1.
  • One circuit per table value, 50/60 Hz, balanced loads. Three-phase circuits are taken as balanced with no neutral current, so the neutral is not a loaded conductor. Harmonic (triplen) currents from drives, LED drivers and IT loads add neutral current and require the reduction factors of IEC 60364-5-52 Annex E, which are not applied.
  • Grouping uses the bunched factors for every method. Table B.52.17 item 1 is the most severe air arrangement; single layers on walls or trays are treated more generously by the standard, and for ducts in the ground its Table B.52.19 applies instead. Check grouped buried runs against that table.
  • No soil correction for D1. The buried values assume a soil thermal resistivity of 2.5 K·m/W and a depth of about 0.7 m; Table B.52.16 corrects for other resistivities and is not applied. Dry sandy soil is worse, moist clay better.
  • No short-circuit or earth-fault check. The conductor must also withstand the let-through energy of the protective device under fault: S = √(I²t) ÷ k with k = 115 for PVC-insulated copper and 143 for XLPE-insulated copper (IEC 60364-4-43, 434.5.2). That calculation, and the earth-fault loop impedance needed for disconnection in time, are not done here.
  • The 1.45 condition assumes a circuit breaker. The coordination check relies on an MCB to IEC 60898-1 or an MCCB to IEC 60947-2, whose conventional tripping current is at most 1.45 × In. Fuses need the 0.9 allowance described under Formula.
  • Voltage drop is resistive, at rated conductor temperature. Cable reactance is ignored, which understates the drop for large conductors at low power factor, and the conductor is assumed to be at 70 °C or 90 °C, which overstates it for a lightly loaded cable. The two errors go in opposite directions; the tabulated mV/A/m values of your wiring rules are the reference where it matters.
  • Tables are for 30 °C air and 20 °C ground. The correction factors run from 10 °C to 60 °C. Above 60 °C PVC has no tabulated factor and the cable should not be there.
  • Not a design review. Mechanical protection, minimum sizes, the sizing of neutral and protective conductors, selectivity and the rules of the local authority (in Pakistan NEPRA's Distribution Code and Consumer Service Manual) are separate matters.

Frequently asked questions

Why derate at all? The catalogue says my 10 mm² cable carries 57 A.

That 57 A is for one circuit in conduit on a wall at 30 °C. The cable can only carry the current that lets it shed its heat while staying at 70 °C. Warmer air removes less heat, so the current has to fall; neighbouring loaded cables heat each other, so it falls again. The factors are not safety margins, they are the physics of the installation, and a cable run at its catalogue rating in a 45 °C roof void with two other circuits is running well above its insulation temperature.

Why size from the breaker rating rather than the load current?

Because the breaker sets the current the cable can be made to carry for hours. If a 25 A load is protected by a 40 A MCB, the cable will not see 25 A when a fault or an added load pushes the circuit up; it will see up to 40 A indefinitely and about 58 A for an hour before the breaker trips. IEC 60364-4-43 therefore requires In ≤ Iz: the cable must be good for the breaker, not just for today's load.

What if the ambient is above the table?

The factors stop at 60 °C for PVC and 80 °C for XLPE in the standard (the calculator stops at 60 °C for both). A cable in a place that hot needs a different route, ventilation, or a heat-resistant cable rated by its manufacturer for that temperature. Note that the temperature to enter is the air around the cable, not the outdoor shade temperature: a conduit on a sun-facing wall or in a closed ceiling void can be 10–15 °C above the room.

Can I use aluminium?

Not with this calculator. Aluminium is tabulated from 16 mm² upward in the same tables at about 75–80 % of the copper current for the same size, has a different resistance and temperature coefficient for voltage drop, and needs terminations designed for it. Size it from the aluminium columns of IEC 60364-5-52 directly.

PVC or XLPE?

For the same conductor, XLPE carries about 30 % more current in air (about 18 % more in the ground) because it can run at 90 °C, and it withstands short circuits better (k = 143 against 115). It costs more per metre but can save a size, which usually wins on long or heavy runs. Two cautions: the 90 °C rating is only usable if the terminals, breakers and busbars it connects to are rated for that temperature, and a cable run at 90 °C drops more voltage than one at 70 °C, which the calculator accounts for.

My cable is a multicore in conduit; which method do I pick?

That is reference method B2, which is not in the calculator. Its capacities are 5–15 % below B1, so choose B1 and then either check the B2 column of the standard or take the next size up if the result is close to its limit.

References

Last reviewed 2026-09-20.